328 WIN-PAK User Guide
Click the Free Egress Input button on the Readers
window. The Configure Free Egress dialog is
displayed:
Only input points can be associated with a Free
Egress Input point, therefore the input (I) point radio
button is automatically selected (and the other two
options are grayed out) on this dialog.
1 Select an Egress Input point that you want to
utilize as the Free Egress Input. Only active
input points that have not been added as ADVs
appear in this list.
2 Enter the Shunt Time for the Egress Point. This
is the amount of time the input point is shunted
[deactivated] when triggered [such as upon a
valid card read].
3 Enter the Debounce Time for the Egress Point.
This is the amount of time that an input must be
in alarm condition [or return to normal] before it
is recognized as an alarm [normal]. For example,
an input with a debounce time of five must be in
alarm condition for five seconds before it is
reported as an alarm. The same is true when
returning to normal condition.